Chimney                  
INDEX || Home || Boiler types || Private house heating || Heating plants || Fuels || Acessories || Design || Selling  || Contact

 Boilers
 
Chimney sizes for CARBOROBOT



For the CARBOROBOT boilers the necessary chimney draught by the stopped ventilator fan is 10-20Pa. This is about 6-7m(18-20 foot) aktíve chimney tube lenght from inlet to the tube end.

Here is some drawings to help to define the chimney
placement
hight
Sizing 1
Sizing 2

Chimneys can be broken down into two main categories; metal and masonry. Metal chimneys, also called prefab.

Metal chimney
6 Inch Inside Diameter (28.3 Square Inches)
7 Inch Inside Diameter (38.5 Square Inches)
8 Inch Inside Diameter (50.3 Square Inches)
10 Inch Inside Dia. (78.6 Square Inches)
One thing that we notice from this table is that a 6" flue is almost 1/2 the size of an 8" flue. The natural tendency might be to think that a 6" flue is "only" two inches smaller that an 8" one, but in truth you can see the difference is much larger.

Masonry Flues
7 1/2 X 7 1/2 (31 Square Inches)
8 1/2 x 8 1/2 (41 Square Inches)
8 1/2 X 13 (70 Square Inches)
13 X 13 (99 Square Inches)
13 X 18 (156 Square Inches)

Masonry and prefab steel tube by the CARBOROBOT power


30-40kW
14x14cm
or insulated stainless tube diameter 130mm (6inch)


60kW
14x20cm
or insulated stainless tube diameter
180mm (6x7inch)


80kW
20x20cm
or insulated stainless tube diameter
180mm (8inch)



120-140kW
20x27cm
or insulated stainless tube diameter
200mm (8x10inch)


180-300kW
27x27cm
or insulated stainless tube diameter
250-300mm (10inch)


Prefab stainless steel chimney

This chimney tubes offered for the CARBOROBOT boilers inner tube material is stainless steel. Cover tube is aluminium. Inner tube diameter between 120- 350mm insulation 30 or 50mm. Possible lenght up to 15m

Chimney parts









Accessories


Insulation 500°C or 1200°C


Console set


Transition flange on the fan


Wall mounting bracket with rubbers

Noise reducing mounting assembly


Transition flange


Fan installation on the noise reducing mounting assembly


Fan installation on the wall without console


Fan installation on the wall mounting bracket

Chimney draw regulator

Automatic regulator for the exhaust chimney

110-130-150-180-200-250 mm diameters
Heat load. max.350 °C.